FISinter (to initial point)
Code Page utf-8
Federative information system of producers on products and services
FISinter

Подсистема «Информация производителей продукции»

Select Language
Information Search
Information Allocation
Details
Настройки браузера
Архив

Processing equipment

Station cooling SO


This brand has modifications - select them below after reading annotation and detailed description

Explanation/Annotation:

For cooling of thyristor frequency converters by the capacity to 800 kilowatt on double-circuit system âîäà/âîäà. Can be èñïîëüçîâàííû for cooling of any electric sets with power losses to 80 kilowatts.

Detailed model description:

The internal closed-circuit shall be filled in the distilled water, the circulation of which is being carried out by the pump, stipulated in box cooling system. In external loop circulates industrial water. is manned by arms and clamps for joining to transducer and suitable pipe-line.

  Detailed modification description
NNModification marking
Inter
Nat.
Ìîøíîñòü rejected losses, kilowatts rated flow of industrial water, ì3/÷ greatest t of cooling tech. water at the output of, with limits of tolerance serf. pressure of tech.. Water, kPa temperature difference of circulating water at the output of and heat-exchanger input, with capacity, consumption electric motors of pump, kilowatt overall dimensions (äëèíà*øèðèíà*âûñîòà), MM mass, kg
1 N 1
N 1
20 3 30 1-3 10 1. 1 360*600*1935 250
2 N 2
N 2
40 6 30 1-3 10 1. 1 780*820*1935 350
3 N 3