Instrumentos de control y regulación, transformadores

Regulador de temperaturas TE2PZ


Para esta marca hay versiones - escójalas abajo después de familiarizarse con el resumen y descripció detallada

Aclaración/resumen:

Electronic. For the automation of systems of ventilation and conditioning of air, in particular in explosive and inflammable premises.

Descripción completa de la marca:

Has the flameproof inlet of sensing circuit (Exia IIc). Provides for two-position or three-position relay-pulse Regulation. Appliance transition in two-position or three-position The operating mode is performed with the help of tumbler, located at the front of. For supervision of work of output equipment in appliance is provided The light indication on light diodes, which are triggered by and are turned off Synchronously with relay. Has built-in the impulse interrupter, that provides Discontinuous instruction input in compliance with set values of duration of pulse and pause. Basic error, °Ñ, not more than, - 1 Pulse duration, controlled, with 0, 5; 1; 2; 3; 4; 5; 6; 8; 10 Pause duration, controlled, with 1; 10; 20; 40; 80; 120; 160; 200; 240; 300 Switching current, but not more than: In case of alternate voltage 12. 220Â, 50Ãö and cosª0, 7 2, 5 In case of constant voltage 12. 220Â 0, 2 Supply voltage by the frequency 50Ãö, in 220 Power consumed, VA, not more than 7 Remoteness, metal, not more than 500 Ambient-air temperature, °Ñ 1. 50 1. 45 Overall dimensions, mm 11õ155õ235 Mass, kg 2 Housing protection of IP20 Is used from the sensor of ÒÑÌ of 50Ì. The sensor in delivery set does not include. Under order the completing from the sensor is possible. In new developments to use ÒÐÝ105È Òåðìîêîð ".

  Versiones/????????????
No.Marcación de la versión
Inter
Nac.
Law of regulationRegulation processes, °ÑReturn zone, controlled, °ÑInsensibility zone, controlled, °Ñ
1 TE2PZ/6
TE2PZ/6
Three-position80. 120-0, 5. 10
2 TE2PZ/5
TE2PZ/5
Three-position60. 100-0, 5. 10
3 TE2PZ/4
TE2PZ/4
Three-position40. 80-0, 5. 10
4 TE2PZ/3
TE2PZ/3
Three-position20. 60-0, 5. 10
5 TE2PZ/2
TE2PZ/2
Two-position0. 400, 5. 10-
6 TE2PZ/1
TE2PZ/1
Two-position- 20. 200, 5. 10-
7 TE2PZ
TE2PZ
Two-position- 40. 00, 5. 10-